The product assortment on this website may differ from what is available where you are located. Do you want to visit the American website instead?

TFL700200+

DC Power Cable

RLAFH, IEC 60332-3-24

  • For outdoor and indoor applications
  • Multistrand class 5 tinned copper 6 mm² or 10 mm²
  • Halogen free
  • Screened with Al foil including two drain wires
  • Jacket of weather proof and fire retardant material
  • Flame retardant IEC 60332-3-24
  • For outdoor and indoor applications
  • Multistrand class 5 tinned copper 6 mm² or 10 mm²
  • Halogen free
  • Screened with Al foil including two drain wires
  • Jacket of weather proof and fire retardant material
  • Flame retardant IEC 60332-3-24

A slim and flexible DC Power cable for FTTA applications or for other telecommunication equipment. To be used indoor or outdoor above ground.

  1. Power cable unit conductor: Stranded tin-plated copper wire class 5, 6 mm² or 10 mm²
  2. Insulation: Flame retardant colored halogen-free thermoplastic compound
  3. Layout: Two insulated conductors in parallel
  4. Screen: Aluminum foil with two drain wires x 2 mm²
  5. Jacket: Flame retardant halogen-free thermoplastic compound

Technical Information

Product Color Black
Temperature, Operation [°C] -40 to +80
Reaction to Fire IEC 60332-3-24 (Cat C)
Voltage Rating [V] 100
Conformance
  • RoHS: 2015/863/EU
  • REACH: EU nr 1907/2006
Marking Manufacturer, year and week ofmanufacture, product No., and length marking
Technical Notes
  • Resistance: 6 mm² - 3.3 Ω/km, 10 mm² - 1.9 Ω/km
  • Screen resistance: 4.95 Ω/km
  • Inductance: 0.6 mH/km
Ordering Information Supplied lengths: On request